Set by the protection level in IEC 62305, which fixes the spacing between conductors around the perimeter: 10 m for Level I, 10 m for Level II, 15 m for Level III, and 20 m for Level IV. Divide the perimeter by that figure. An NFC 17-102 ESE installation needs at least two down conductors once the structure exceeds 28 m in height.
Copper for anything entering the ground, in damp locations, and in coastal or industrial air. Aluminium for above ground runs where weight and cost matter, but never in contact with soil, mortar, or plaster, because it corrodes rapidly in both. Where the run changes from aluminium to copper, use a bimetallic connection above ground and keep it accessible.
Lightning current is a fast rising impulse, and inductance rather than resistance controls the voltage along the run. A sharp bend raises inductance and can cause the current to flash across the corner instead of following the conductor. Keep bends gradual, with a bending radius of at least 20 cm, and take the shortest, straightest route to earth.
The minimum air gap between the down conductor and nearby metalwork, pipes, cable trays, and building services, calculated per IEC 62305-3. Below that gap, the lightning current can jump across and enter the building services. Where you cannot achieve the distance, either bond the metalwork to the system or use insulated conductor.
Yes. Fit a disconnection joint about 1.5 to 2 m above ground on every down conductor, so continuity to the earth electrode can be measured individually. Without it, the annual inspection can only test the whole system in parallel and cannot find the one run that has failed.