1 Hole, Long Barrel (mm2)

1 Hole Long Barrel Aluminium Lug designed for secure termination of metric aluminium conductors. The long barrel provides an extended crimping area, while the barrel is pre-filled with oxide-inhibiting compound and capped at the end.
Power Distribution
Crimp Terminal
Aluminium Lug
Metric Cable Lug
1 Hole Lug
Oxide Inhibiting Compound
Bright Finish
Electro-Tinned Finish
16–1000 mm²
Electrical Termination

Selection Summary

Cable : 16–1000 mm²

Material : Electrolytic Grade Aluminium 99.5

Barrel : Long Barrel

Finish : Bright / Electro-Tinned

Feature : Pre-filled with Oxide Inhibiting Compound

Application Check

Is this product right for your application?

Application

Suitable?

Recommendation

Metric Aluminium Conductor
Yes
Select the lug according to cable size
16–1000 mm² Cable
Yes
Choose the matching conductor size
1-Hole Termination
Yes
Suitable for single-stud mounting
Long Barrel Required
Yes
Provides an extended crimping section
Oxide-Inhibiting Compound Required
Yes
Barrel is supplied pre-filled
Copper Conductor
No
Use the applicable Copper Cable Lug range

SPECIFICATIONS

Technical Specifications

Product Code Cable Size mm2 Stud Size ∅E Dimensions in mm
A C D P B L
AAH0016M08 16 8.2 5.5 11 20 21 41 69
AAH0016M10 16 10.5 5.5 11 20 21 41 69
AAH0025M08 25 8.2 6.5 15 22 21 41 69
AAH0025M10 25 10.5 6.5 15 22 21 41 69
AAH0035M10 35 10.5 8 15 25 22 50 79
AAH0035M12 35 13 8 15 25 22 50 79
AAH0050M10 50 10.5 9.7 18 26 24 50 81
AAH0050M12 50 13 9.7 18 26 24 50 81
AAH0070M10 70 10.5 11 18 26 26 62 95
AAH0070M12 70 13 11 18 26 26 62 95
AAH0095M10 95 10.5 13.1 20 29 28 73 109
AAH0095M12 95 13 13.1 20 29 28 73 109
AAH0095M16 95 17 13.1 20 29 28 73 109
AAH0120M12 120 13 14.7 22 32 30 73 114
AAH0120M16 120 17 14.7 22 32 30 73 114
AAH0150M12 150 13 16.5 25 36 34 83 128
AAH0150M16 150 17 16.5 25 36 34 83 128
AAH0150M20 150 21 16.5 25 36 34 83 128
AAH0185M12 185 13 18.1 28 45 36 83 131
AAH0185M16 185 17 18.1 28 45 36 83 131
AAH0185M20 185 21 18.1 28 45 36 83 131
AAH0240M12 240 13 21 28 45 44 86 144
AAH0240M16 240 17 21 28 45 44 86 144
AAH0240M20 240 21 21 28 45 44 86 144
AAH0300M16 300 17 23.2 34 55 54 89 157
AAH0300M20 300 21 23.2 34 55 54 89 157
AAH0400M16 400 17 26 38 55 60 113 187
AAH0400M20 400 21 26 38 55 60 113 187
AAH0500M16 500 17 29 45 65 64 125 205
AAH0500M20 500 21 29 45 65 64 125 205
AAH0630M16 630 17 33.5 45 65 68 140 225
AAH0630M20 630 21 33.5 45 65 68 140 225
AAH0800M20 800 21 37.6 58 84 78 147 250
AAH0800M25 800 21 37.6 58 84 78 147 250
AAH1000M20 1000 21 41.5 60 87 90 160 280
AAH1000M25 1000 21 41.5 60 87 90 160 280

Request Quotation

FAQS

Frequently Asked Questions

Find quick answers to common questions about our programs, admissions, eligibility, and application process to help you move forward with confidence.

Not without protection. Aluminium against copper in the presence of moisture sets up galvanic corrosion, and joint resistance climbs until the connection runs hot. Use a bimetallic lug, a tin plated palm, or a bimetallic washer at the interface.
Aluminium forms an oxide film the moment it meets air, and that film is a poor conductor. Wire brush the strands, apply the inhibitor compound, and crimp immediately. The compound breaks through what remains of the film and keeps air out afterwards. Skip this step and the joint starts sound, then degrades over the following months.
A full tension joint carries the mechanical pull of the span as well as the current, so it can sit mid span between poles. A standard compression joint carries current only and needs the conductor supported elsewhere. Never use a non tension joint inside a span.
Aluminium creeps under sustained clamping pressure, so a bolted joint can lose contact force over time. Use the torque value on the datasheet and check bolted terminations at the first maintenance visit. Compression joints do not creep, which is one reason they are specified on permanent connections.
Heat cycling. A fresh joint almost always measures well, so the meaningful test loads the connection repeatedly and reads contact resistance after each cycle, showing whether it stays stable as aluminium expands, contracts, and creeps. Axis runs heat cycling alongside tensile, pull out, torque, and contact resistance testing in its NABL accredited lab.

Download Catalogue